Hawke ICG 653/Universal cable glands are suitable for use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.
For particular use with:-
a) Cable inner sheaths that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit ‘cold flow’ characteristics.
c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area.
Hawke ICG 653/Universal cable glands are dual certified Exd and Exe and suitable for installation in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC, 5.5-78.0mm outside cable diameters.
When used in increased safety applications the Hawke cable gland can be used to terminate braided cables where the braid and the cable outer sheath enter into the electrical enclosure or junction box.
? Exdb IIC Gb, Exe IIC Gb, Extb IIIC, Db Aromoured Cables ATEX & IECEx Cable Gland.
Hawke ICG 653/Universal cable gland is suitable for cable termination and installation in Zone 1 (21), Zone 2 (22) and Division 2 hazardous areas.
Hawke Size Ref. | Entry Thread Size | Cable Acceptance Details | ‘G’ Compressed Length | Hexagon Dimensions | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inner Sheath/ Cores | ‘B’ Outer Sheath | ‘C’ Armour/Braid | ||||||||||||
Metric | NPT * | ‘D’ Max. Over Cores | ‘E’ Max. Inner Sheath | NOTE 1 Max. No. Of Cores | NOTE 2 Max. No. Of Cores | Across Flats | Across Corners | |||||||
Standard | Option | Min. | Max. | Orientation 1 | Orientation 2 | |||||||||
Os | M20 | ?” | – | 8.9 | 10.0 | 12 | 6 | 5.5 | 12.0 | 0.8 / 1.25 | 0 / 0.8 | 67.0 | 24.0 | 26.5 |
O | M20 | ?” | – | 8.9 | 10.0 | 12 | 6 | 9.5 | 16.0 | 0.8 / 1.25 | 0 / 0.8 | 67.0 | 24.0 | 26.5 |
A | M20 | ?” | ?” | 11.0 | 12.5 | 15 | 10 | 12.5 | 20.5 | 0.8 / 1.25 | 0 / 0.8 | 67.0 | 30.0 | 32.5 |
B | M25 | 1″ | ?” | 16.2 | 18.4 | 30 | 21 | 16.9 | 26.0 | 1.25 / 1.6 | 0 / 0.7 | 73.6 | 36.0 | 39.5 |
C | M32 | 1?” | 1″ | 21.9 | 24.7 | 42 | 42 | 22.0 | 33.0 | 1.6 / 2.0 | 0 / 0.7 | 78.0 | 46.0 | 50.5 |
C2 | M40 | 1?” | 1?” | 26.3 | 29.7 | 60 | 60 | 28.0 | 41.0 | 1.6 / 2.0 | 0 / 0.7 | 82.4 | 55.0 | 60.6 |
D | M50 | 2″ | 1?” | 37.1 | 41.7 | 80 | 80 | 36.0 | 52.6 | 1.8 / 2.5 | 0 / 1.0 | 88.7 | 65.0 | 70.8 |
E | M63 | 2?” | 2″ | 47.8 | 53.3 | 100 | 100 | 46.0 | 65.3 | 1.8 / 2.5 | 0 / 1.0 | 92.7 | 80.0 | 88.0 |
F | M75 | 3″ | 2?” | 59.0 | 66.2/65.3 ? | 120 | 120 | 57.0 | 78.0 | 1.8 / 2.5 | 0 / 1.0 | 99.4 | 95.0 | 104.0 |
CABLE GLAND MATERIAL & FINISH
Hawke ICG 653/Universal cable glands are manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
Strip Cable to suit equipment as shown above and expose the armour/braid ‘I’ removing all cable fillers.
‘I’ = 20mm for cable gland sizes Os to A ‘I’ = 25mm for cable gland sizes B to C2 ‘I’ = 32mm for cable gland sizes D to F ‘II’ to suit equipment. If required, fit shroud.
Push the cable through the armour spigot (4). Spread armour/braid over the armour spigot (4) until the end of the armour/braid is up against the shoulder of the armour cone. Position the armour clamping ring (3).
Remove the inner seal (5) from the entry (6). Place the entry (6) over the armour spigot (4). Move the sub-assembly (1) and (2) up to meet the entry (6).
Hawke Cable Glands to view the complete range of hazardous area glands certified according to ATEX & IECEx for Zone 1 / Zone 2.
Hawke帶膠泥鎧裝防爆格蘭(ICG653/UNIV)